BExH120 'Belltronic' Explosion Proof Bell
The flameproof BExH120 Belltronic Signalling Bell is suitable for Zone 1, 2, 21 & 22 applications. Approved to IECEx, ATEX, Ex EAC and INMETRO standards. The BExH120 authentically reproduces the traditional sound of a electro-mechanical bell whilst providing a significantly higher level of performance and reliability.
The digitally stored bell recording is output via a class D amplifier achieving sound levels exceeding the performance of a mechanical bell whilst offering a continuously rated signal. The radial horn design not only physically emulates the traditional bell it also replicates the distribution of the audible signal.
Features:
• Marine grade, corrosion proof, LM6 aluminium enclosure.
• Ingress protection IP66/67
• Stainless steel fixings
• Dual M20 cable entries - adaptors available.
• Stopping plug included.
• Reverse polarity diode fitted.
• Digitally stored mechanical bell sound.
• Continuously rated.
• Maintenance free.
• Very large termination area.
• Ratchet adjustable stainless steel ‘U’ bracket.
Approvals:
IECEx KEM 10.0003X
IEC 60079-0 : 2011
IEC 60079-1 : 2007-4
IEC 60079-31 : 2013
ATEX KEMA 99ATEX6312X
EN 60079-0 : 2012 + A11
EN 60079-1 : 2007
EN 60079-31 : 2014
TR-CU Ex EAC certificate: RU C-GB.AA71.B.00109
Safety-integrity suitability: SIL1
Inmetro certificate: 10-IEx-0009
Coding:
• II 2G Ex d IIB T4 Ta -50° to +70°C
• II 2G Ex d IIC T4 Ta -50° to +55°C
• II 2D Ex tb IIIC T100°C Db Ta -50°C to +55°C
• II 2D Ex tb IIIC T115°C Db Ta -50°C to +70°C
Specification:
Nominal output: | 106dB(A) @ 1m +/- 3dB [97dB(A) @ 10ft/3m] |
Volume control: | Yes |
Voltages DC: | 24vDC |
Voltages AC: | 115vAC; 230vAC |
Stage switching: | Negative |
Ingress protection: | IP66/67 |
Enclosure matl: | Marine grade copper free LM6 Aluminium |
Enclosure finish: | Chromate & powder coated finish - anti-corrosion. |
Colour: | Red RAL3000 |
| Grey RAL7038 (and black radial horn) |
| Special - available on request |
BExH120 horn: | High impact UL94 V0 & 5VA FR ABS |
Cable entries: | Dual M20 ISO (one stopping plug inc) |
Terminals: | 0.5 - 2.5mm² (20-14 AWG) |
Enclosure volume: | < 2 litres |
Line monitoring: | Blocking diode included |
| EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor |
| or diode (DC versions) can be fitted |
Weight: | DC: 3.20kg/7.04Ibs AC: 3.40kg/7.48Ibs |
Current Consumption:
Voltage: | | Current: |
| | |
24vDC | | 400mA |
115vAC | 50/60Hz | 130mA |
230vAC | 50/60Hz | 65mA |
Part Codes: | BExH120 DR [u] [e] [m] [s] [v] [x] |
Version: | Part code: | |
| | |
Product type: | BExH120 | Explosion proof Belltronic |
| | |
Type: | DR | Ex d, Radial omni-directional horn |
| | |
Voltage: [u] | DC024 | 24vDC |
| AC115 | 115vAC |
| AC230 | 230vAC |
| | |
Cable Entry Type: [e] | A | 2 x M20x1.5mm (Standard) |
| B | 2 x 1/2" NPT - adaptors |
| C | 2 x 3/4" NPT - adaptors |
| D | 2 x M25x1.5mm - adaptors |
| E | 1 x 1/2" NPT - adaptor |
| F | 1 x 3/4" NPT - adaptor |
| G | 1 x M25x1.5mm - adaptor |
| Note: | M20 stopping plugs for unused |
| | entries supplied with all options |
| | |
Adaptor/Stopping | B | Brass (Standard) |
plug material: [m] | N | Nickel Plated |
| S | Stainless Steel |
| | |
Bracket material: [s] | 1 | A2 304 Stainless Steel (Standard) |
| 2 | A4 316 Stainless Steel |
| 3 | A2 304 St/St with Equip. Tag |
| 4 | A4 316 St/St with Equip. Tag (304) |
| | |
Product version: [v] | A1 | Default - IECEx, ATEX, Ex EAC |
| | & INMETRO |
| | |
Enclosure colour: [x] | R | Red RAL3000 (Standard) |
| G | Grey RAL7038 (and black radial horn) |
| S | Special - contact us! |
Tone Table:
Stage 1 | WAV file | Frequency Description | Stg 2 | Stg 3 |
| | | | |
T 1 | | Industrial Hooter | T 3 | T 5 |
T 2 | | High Frequency Mechanical Siren | T 1 | T 5 |
T 3 | | Medium Frequency Mechanical Siren | T 1 | T 5 |
T 4 | | Electro Mechanical Buzzer | T 2 | T 5 |
T 5 | | Mechanical Bell | T 1 | T 2 |
| | | | |
Country specific or custom tone configurations and alarm frequencies are available upon request.