GNExCP6A-BG Break Glass Manual Call Point - RED
The GNExCP6A manual call points are available as break glass, push button or tool reset versions. They are approved for Zone 1, 2, 21 and 22 hazardous areas for the control of fire and gas alarm systems.
Available with either single or double pole change over switches. All versions are certified to ATEX and IECEx standards.
Specification: | |
GNExCP6A: | II 2G Ex e d IIC T6 Gb |
| II 2D Ex t IIIC T60°C Db |
| IP66 |
Ambient: | Ta = -40°C to +55°C [-40°to +131°F] |
Ingress protection: | IP66 |
Housing material: | GRP - glass reinforced polyester (UV stable) |
Colour: | RAL3000 Red (others available on request) |
Cable entries: | 2 x M20 clearance top and 1 x M20 clearance side. |
| Back box can be rotated to give |
| 2 x bottom and 1 x side entries. |
Stopping plugs: | 2 x Ex e nylon plugs as standard |
| Brass and stainless steel plugs optional |
Terminals: | 6 x 4.0mm² cables. |
Test: | Test key facility |
Weight: | 1.2Kg/2.64Ibs |
Note: | For applications requiring monitoring |
| resistors, diodes or inidcator LED’s |
| please see the GNExCP6B-BG version. |
| Data sheet reference: 1.3.07. |
Part Codes:
(The actual choices for this particular model are highlighted in red)
Version: | Part code: | |
| | |
Product type: | GNExCP6A | A type - no end of line devices |
| | |
Type: | BG | Break Glass |
| | |
Switch Type: [s] | S | SPCO (Single Pole) |
| D | DPCO (Double Pole) |
| | |
Stopping | N | Nylon |
plug material: [m] | B | Brass |
| P | Nickel Plated |
| S | Stainless Steel |
| | |
Lift flap: [l] | N | No lift flap |
| L | Lift flap |
| | |
Duty label: [d] | N | No duty label |
| P | Metalised Polyester |
| S | Stainless Steel |
| | |
Enclosure colour: [x] | RD | Red |
| BL | Blue |
| GN | Green |
| YW | Yellow |
| RW | Red/White |
| YB | Yellow/Black |
| BK | Black |
Example part code: | GNExCP6A-BG [s] [m] [l] [d] [x] |
Makes this part code : | GNExCP6A-BG-S-S-L-S-RD |
| |
Explanation of above | |
Product type: | "GNExCP6A" = Call Point A type |
| - no end of line devices |
Type: | "BG" = Break Glass type |
Switch type: [s] | "S" = SPCO (Single Pole) |
Stopping plug: [m] | "S" = Stainless Steel stopping plug |
Lift flap: [l] | "L" = Lift flap |
Duty label: [d] | "S" = Stainless Steel Duty label |
Enclosure colour: [x] | "RD" = Red enclosure |
Options
• Alternative housing colours are available to meet specific requirements.
• Single or double pole c/o switch.
• Metalised polyester or stainless steel “Duty” label.
Coding: II 2G Ex e d IIC T6 Gb Ta = -40°C to +55°C
II 2D Ex t IIIC T60°C Db IP66
Approvals
ATEX certificate: Sira 09ATEX3286X, IEC 60079-0:2007 Ed 5, EN 60079-1:2004, EN 60079-7:2007, IEC 60079-18:2009 Ed 3, EN 61241-1:2004
IECEx certificate: IECEx SIR 09.0121X, IEC 60079-0:2007-10 Edition: 5, IEC 60079-1:2003 Edition: 5, IEC 60079-18:2009 Edition: 3, IEC 60079-7:2006-07 Edition: 4, IEC 61241-1:2004 Edition: 1