GNExS1 Alarm Horn Sounder 117dB(A)
The flameproof GNExS1 alarm sounder is suitable for Zone 1 & Zone 2 applications - certified to ATEX and IECEx.
Sound level ouputs are up to 117dB(A) at 1 metre with a choice of 45 alarm tones and 4 remotely selectable stages. The alarm tone frequencies for the first 2 stages are independently selectable. The GNEx range features enclosures manufactured from GRP (glass reinforced polyester), moulded in natural red, but also available in other colours.
The re-entrant flare horn is high impact, fire retardant ABS. All models have two M20 cable entries, large termination areas containing in & out terminals and an ingress protection of IP66/67.
Features:
• Automatic synchronisation on multi-sounder system.
• Very large termination area.
• Ratchet adjustable stainless steel ‘U’ bracket.
• IN & OUT terminals.
• Independently selectable tones for 1st & 2nd stages.
Approvals:
ATEX certificate:
SIRA 13ATEX1139X, EN 60079-0 : 2012, EN 60079-1 : 2007
IECEx certificate:
IECEx SIR 13.0029X, IEC 60079-0 : 2011 (Ed6), IEC 60079-1 : 2007 (Ed6)
Coding:
• II 2G Ex d IIC T4 Ta. -60° to +50°C
• II 2G Ex d IIC T3 Ta. -60° to +70°C
• II 2G Ex d IIB T6 Ta. -60° to +50°C
• II 2G Ex d IIB T5 Ta. -60° to +65°C
• II 2G Ex d IIB T4 Ta. -60° to +70°C
Specification:
Maximum output: | 117dB(A) @ 1 metre [108dB(A) @ 10ft/3m] |
Nominal output: | 110dB(A) @ 1m +/- 3dB - Tone 2 |
| [101dB(A) @ 10ft/3m] |
No. of tones: | 45 (UKOOA / PFEER compliant) |
No. of stages: | 4 |
Volume control: | Max. 110dB(A); Min. 72dB(A) - Tone 2 |
Effective range: | 100m/328ft @ 1KHz |
Voltages DC: | 24vDC (10-30vDC), 48vDC (38-60vDC) |
Voltages AC: | 230vAC (100-260vAC/DC) |
Stage switching: | Negative or positive |
Ingress protection: | IP66/67 |
Enclosure matl: | GRP (glass reinforced polyester) |
Colour: | RAL3000 Red |
| (others available on request) |
Flare matl: | High impact UL94 V0 & 5VA FR ABS (Red) |
Cable entries: | Dual M20 ISO |
| Adaptors to M25, 1/2" & 3/4" NPT can be specified |
Terminals: | 0.5 - 2.5mm² (20-14 AWG) |
Enclosure volume: | <2 litres |
Line monitoring: | Blocking diode included |
| EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor |
| or diode (DC versions) can be fitted |
Weight: | DC: 3.00kg/6.6Ibs AC: 3.20kg/7.04Ibs |
Part Codes: GNEx S1 [u] [m] [s] [v] [x]
Version: | Part code: | |
| | |
Product type: | GNEx S1 | |
| | |
Voltage: [u] | DC024 | 24vDC (10-30vDC) |
| DC048 | 48vDC (38-60vDC) |
| AC230 | 230vAC (110-260vAC) |
| | |
Adaptor/Stopping | B | Brass |
plug material: [m] | N | Nickel Plated |
| S | Stainless Steel (Standard) |
| | |
Bracket material: [s] | 1 | A2 304 Stainless Steel |
| 2 | A4 316 Stainless Steel (Standard) |
| 3 | A2 304 St/St with Equip. Tag |
| 4 | A4 316 St/St with Equip. Tag (304) |
| | |
Product version: [v] | A1 | Group II 2G/D Zone 1, 2, 21 & 22 |
| | (Standard) |
| | |
Enclosure colour: [x] | R | Red RAL3000 (Standard) |
| S | Special colour - contact sales |
Example part code: | GNEx S1 [u] [m] [s] [v] [x] |
| GNEx S1 DC024 S 2 A1 R |
| |
Explanation of tehe above: | |
Product type: | "GNEx S1" |
Voltage: [u] | "DC024" = 24vDC (10-30vDC) |
Stopping plug: [m] | "S" = Stainless Steel |
Bracket material: [s] | "2" = A4 316 Stainless Steel Bracket |
Product version: [v] | "A1" = Group II 2G/D Zone 1, 2, 21 & 22 |
Enclosure colour: [x] | "R" = Red Enclosure colour |
Current Consumption:
Version: | | Voltage: | Current: |
24vDC | | 10-30vDC | 140mA @ 24vDC |
48vDC | | 38-60vDC | 73mA @ 48vDC |
115vAC | 50/60Hz | 100-260vAC | 86mA @ 115vAC |
230vAC | 50/60Hz | 100-260vAC | 75mA @ 230vAC |